Liquid-immersed power and distribution transformers

New-manufacture units up to 50 MVA, designed for 60 Hz service and built to the IEEE C57 series. Every unit is routine tested per IEEE C57.12.90 and delivered with test certificates issued against its serial number.

Interactive

Anatomy of the unit

Select a numbered point to see what it is and how it is specified. Diagram is a schematic elevation, not a drawing of a specific unit.

1 2 3 4 5 6 7 8 9

Drag to orbit · scroll to zoom · click a component

Select a point

Nine points on the unit

Tap or click any numbered marker on the diagram to see what that component is and how it gets specified on an order.

Tap a marker on the diagram, use the buttons below, or tab to a marker and press Enter.

Expansion tank that keeps the core and windings covered with insulating liquid as the oil volume changes with load and ambient temperature. Fitted with a dehydrating breather so the oil is not exposed to moist air.

Specified as part of the accessory scope at quotation.

Insulated terminations that carry the primary conductors through the tank wall. The voltage class determines the creepage distance and therefore the physical size of the bushing.

Primary voltage class is confirmed against your specification before quotation.

Secondary terminations. Shorter than the HV bushings because the insulation requirement is lower, and usually carrying substantially higher current.

Secondary voltage class and current rating confirmed at quotation.

Stacked laminations of grain-oriented electrical steel forming the magnetic circuit. The core is the dominant contributor to no-load loss, which is present whenever the unit is energised regardless of load.

Core design is fixed for 60 Hz at the design stage. A 50 Hz core is not modified to run at 60 Hz — it is a different design.

High- and low-voltage windings arranged concentrically around each core limb. The windings dominate load loss, which varies with the square of the load current, and they set the impedance.

Both no-load and load loss are guaranteed values in our quotations, backed by liquidated-damages language and verified by the routine test on your unit.

Sealed steel enclosure holding the core, windings and insulating liquid. Leak and pressure testing of the tank forms part of the routine test sequence.

Metal-enclosed and substation-type construction per IEEE C57.12.10.

Detachable cooling panels that dissipate heat from the insulating liquid. The cooling class determines whether circulation is natural or assisted by fans or pumps, and therefore what continuous rating the unit will carry.

Cooling class and any overload duty are confirmed against your specification.

Houses the tap-changing mechanism. A de-energised tap changer is operated with the unit off supply; an on-load tap changer adjusts under load. Which one applies, and the tap range and step size, follow your specification.

Tap arrangement is one of the items we ask for in an enquiry.

Records rating, voltage class, impedance, frequency, cooling class, liquid volume and the unit's serial number.

The serial number is the link between the physical unit and its routine test certificate — which is why we issue certificates per serial number rather than per order.

Specification summary

Supply scope

New-manufacture liquid-immersed power and distribution transformers
ProductNew-manufacture liquid-immersed power and distribution transformers
Rating rangeUp to 50 MVA. Core commercial focus is the 12–50 MVA class.
Design standardsIEEE C57.12.00 — general requirements for liquid-immersed distribution, power and regulating transformers
IEEE C57.12.10 — metal-enclosed / substation transformers
Test standardIEEE C57.12.90 — test code for liquid-immersed transformers
Routine testsPerformed on every unit; certificates issued per serial number
Factory acceptanceWitnessed by an independent third-party inspection agency; customer or customer-appointed inspector welcome
Loss performanceGuaranteed no-load and load loss values, quoted with liquidated-damages language
Frequency60 Hz
Typical lead timeApproximately 8 months from order release
Delivery termsDDP to site is quotable. Other Incoterms 2020 arrangements can be quoted on request.

Interactive

Loss-evaluation calculator

Municipal utilities and cooperatives rarely award on first cost. Losses are capitalised over the life of the unit and added to the purchase price to give an evaluated cost. Enter your own figures and rates below.

Total ownership cost

Evaluated cost calculator

$
Leave blank to see the capitalised loss value on its own.
W
W
$/W
$/W

Rates default to the values published by ElectriCities of North Carolina in its own bid documents — a widely used public example of the practice. Replace them with the rates your own procurement applies.

Evaluated cost
Enter loss figures to evaluate.
Purchase price No-load loss Load loss
Purchase price
Capitalised no-load loss
Capitalised load loss
Losses as share of evaluated cost
Formula: evaluated cost = purchase price + (no-load loss W × $/W) + (load loss W × $/W). Attributed to ElectriCities of North Carolina as a published example of standard loss-evaluation practice; it is not our methodology, and the capitalisation rates applied to your procurement are yours to set. This tool performs arithmetic on figures you enter and does not transmit them anywhere.

We quote guaranteed no-load and load loss values, with liquidated-damages backing, precisely so they can be entered into a formula of this kind as firm numbers. A supplier who will not guarantee losses cannot be evaluated on this basis, and on a loss-evaluated bid that is usually decisive.

Interactive

Where does your rating land?

Rating drives three separate things at once: whether we can supply it, which tariff subheading it falls under, and whether DOE efficiency rules apply. Drag to see all three.

Rating & classification

15 MVA

110255055 MVA
Our supply
Core focus
HTS subheading
8504.23
Section 232 duty
15%
DOE 10 CFR 431
Out of scope

Classification boundaries are 10,000 kVA for the HTS subheading and 2,500 kVA for DOE scope. Duty rates change and classification is confirmed per order with our customs broker — see Trade & Compliance.

Scope

Configuration is quoted against your specification

We do not publish a fixed catalogue. Rating, voltage class, impedance, cooling class, tap arrangement, bushing and accessory scope, and enclosure requirements are confirmed against the purchaser's specification at the time of quotation, together with the applicable standard revision.

If you are working to a utility standard specification, send it with the enquiry. We will respond with a clause-by-clause confirmation of compliance and an explicit list of any exceptions rather than a blanket statement of conformity.

What to include in an enquiry

  • Rating (MVA) and voltage class, primary and secondary
  • Impedance requirement and tolerance
  • Cooling class and any loading or overload duty
  • Tap arrangement — de-energised or on-load, range and steps
  • Quantity, delivery location and required on-site date
  • Governing standard specification, if you have one
  • Whether the project carries domestic-content requirements — see Trade & Compliance

Technical notes

Points that come up regularly

Real engineering questions we get asked, answered without hedging.

Units intended for US service are designed for 60 Hz from the outset — a different core design, not a modified 50 Hz core. Frequency is fixed at the design stage and is stated on the test certificate and nameplate.

Request a quotation

Send your specification and required dates. You will get confirmation of what we can quote today, the current lead time, and any exceptions to your specification.

Request a quotation Call